Comparison Study of Novel Flat Evaporator Loop Heat Pipes with Different Types of Condensation Pipeline

Author

Listed:
  • Kangning Xiong

    (State Key Laboratory of Green Building, School of Building Services Science and Engineering, Xi’an University of Architecture and Technology, Xi’an 710055, China)

  • Yang Liu

    (State Key Laboratory of Green Building, School of Building Services Science and Engineering, Xi’an University of Architecture and Technology, Xi’an 710055, China)

  • Zhuoyu Li

    (State Key Laboratory of Green Building, School of Building Services Science and Engineering, Xi’an University of Architecture and Technology, Xi’an 710055, China)

  • Qingsong Pan

    (State Key Laboratory of Green Building, School of Building Services Science and Engineering, Xi’an University of Architecture and Technology, Xi’an 710055, China)

Abstract

Chip-level cooling has become a thermal bottleneck in next-generation data centers. Although previous studies have optimized evaporator wick structures, they are limited to a single condensation path and ignore the combined effects of the loop heat pipe (LHP) orientation on the capillary wick (CW) replenishment and reflux subcooling. To bridge this gap, this study successfully designed an innovative flat-plate evaporator water-cooled LHP with a parallel condensation pipeline. Experiments were conducted with a 20 °C coolant and at a 4 L/min flow rate across nine orientations. The heat transfer characteristics of LHPs with parallel and series condensation pipelines were compared. The analysis focused on the relationship between the working fluid (WF) replenishment of the CW and the WF reflux temperature in the compensating chamber (CC). The experimental results demonstrated that the parallel condensation LHP could sustainably dissipate 750 W without thermal runaway. At this power, the minimum junction temperature of 82.34 °C was measured at orientation 2 (+60°). For low power and at the nine orientations, the series LHP generally had lower temperatures. However, when the power exceeded 600 W, the parallel LHP showed lower temperatures at orientations 1 (+90°), 2 (+60°), and 3 (+30°). At orientation 9, the parallel LHP had lower temperatures when the power surpassed 200 W. Theoretical analysis indicated that the orientation changes affected the heat transfer via the WF reflux temperature, reflux resistance, and CW replenishment rate. Furthermore, the LHP system we developed in this study is capable of fully satisfying the cooling requirements of data center server chips.

Suggested Citation

  • Kangning Xiong & Yang Liu & Zhuoyu Li & Qingsong Pan, 2025. "Comparison Study of Novel Flat Evaporator Loop Heat Pipes with Different Types of Condensation Pipeline," Energies, MDPI, vol. 18(16), pages 1-27, August.
  • Handle: RePEc:gam:jeners:v:18:y:2025:i:16:p:4247-:d:1721284
    as

    Download full text from publisher

    File URL: https://www.mdpi.com/1996-1073/18/16/4247/pdf
    Download Restriction: no

    File URL: https://www.mdpi.com/1996-1073/18/16/4247/
    Download Restriction: no
    ---><---

    References listed on IDEAS

    as
    1. Kargar, Sajad & Moran, Jeffrey L., 2025. "Combining direct and indirect free cooling for data centers via transformation into a building-scale heat exchanger," Applied Energy, Elsevier, vol. 392(C).
    2. Zhou, Guohui & Li, Ji & Jia, Zizhou, 2019. "Power-saving exploration for high-end ultra-slim laptop computers with miniature loop heat pipe cooling module," Applied Energy, Elsevier, vol. 239(C), pages 859-875.
    3. Danyang Li & Jie Song & Hui Liu & Jingqing Jiang, 2024. "Simulators for Conversing Power to Thermal on Green Data Centers: A Review," Energies, MDPI, vol. 17(22), pages 1-24, November.
    4. Yan Bai & Lijun Gu & Xiao Qi, 2018. "Comparative Study of Energy Performance between Chip and Inlet Temperature-Aware Workload Allocation in Air-Cooled Data Center," Energies, MDPI, vol. 11(3), pages 1-23, March.
    5. Li, Nan & Li, Haowei & Duan, Kaiwen & Tao, Wen-Quan, 2025. "Evaluation of the cooling effectiveness of air-cooled data centers by energy diagram," Applied Energy, Elsevier, vol. 382(C).
    6. Yihang Zhao & Mingshan Wei & Dan Dan, 2024. "Modeling, Design, and Optimization of Loop Heat Pipes," Energies, MDPI, vol. 17(16), pages 1-40, August.
    7. Jung, Eui Guk & Boo, Joon Hong, 2020. "Experimental observation of thermal behavior of a loop heat pipe with a bypass line under high heat flux," Energy, Elsevier, vol. 197(C).
    8. Yongle Tang & Xuewei Zhang & Zhichun Liu, 2023. "Experimental Study on the Thermal Performance of Flat Loop Heat Pipe Applied in Data Center Cooling," Energies, MDPI, vol. 16(12), pages 1-21, June.
    9. Hongzhe Zhang & Fang Ye & Hang Guo & Xiaoke Yan, 2022. "Isothermal Performance of Heat Pipes: A Review," Energies, MDPI, vol. 15(6), pages 1-16, March.
    10. Ying Wang & Xiang Huang & Junjie Chu & Yan Du & Xing Tang & Cong Dai & Gang Ma, 2022. "Analysis of an Evaporative Condensation System Coupled to a Microchannel-Separated Heat Pipe for Data Centers," Energies, MDPI, vol. 15(23), pages 1-18, November.
    Full references (including those not matched with items on IDEAS)

    Most related items

    These are the items that most often cite the same works as this one and are cited by the same works as this one.
    1. Ghadim, H. Benisi & Godin, A. & Veillere, A. & Duquesne, M. & Haillot, D., 2025. "Review of thermal management of electronics and phase change materials," Renewable and Sustainable Energy Reviews, Elsevier, vol. 208(C).
    2. Yeliang Qiu & Congfeng Jiang & Yumei Wang & Dongyang Ou & Youhuizi Li & Jian Wan, 2019. "Energy Aware Virtual Machine Scheduling in Data Centers," Energies, MDPI, vol. 12(4), pages 1-21, February.
    3. Jin, Chaoqiang & Bai, Xuelian & Yang, Chao & Mao, Wangxin & Xu, Xin, 2020. "A review of power consumption models of servers in data centers," Applied Energy, Elsevier, vol. 265(C).
    4. Jiwen Cen & Feng Li & Tingliang Li & Wenbo Huang & Juanwen Chen & Fangming Jiang, 2021. "Experimental Study of the Heat-Transfer Performance of an Extra-Long Gravity-Assisted Heat Pipe Aiming at Geothermal Heat Exploitation," Sustainability, MDPI, vol. 13(22), pages 1-16, November.
    5. Marco Bernagozzi & Nicolas Miché & Anastasios Georgoulas & Cedric Rouaud & Marco Marengo, 2021. "Performance of an Environmentally Friendly Alternative Fluid in a Loop Heat Pipe-Based Battery Thermal Management System," Energies, MDPI, vol. 14(22), pages 1-19, November.
    6. Wang, Xinyue & Liu, Yang & Tian, Tong & Li, Ji, 2022. "Directly air-cooled compact looped heat pipe module for high power servers with extremely low power usage effectiveness," Applied Energy, Elsevier, vol. 319(C).
    7. Sijun Xu & Hua Zhang & Zilong Wang, 2023. "Thermal Management and Energy Consumption in Air, Liquid, and Free Cooling Systems for Data Centers: A Review," Energies, MDPI, vol. 16(3), pages 1-25, January.
    8. Tian, Tong & Wang, Xinyue & Liu, Yang & Yang, Xuan & Sun, Bo & Li, Ji, 2023. "Nano-engineering enabled heat pipe battery: A powerful heat transfer infrastructure with capability of power generation," Applied Energy, Elsevier, vol. 348(C).
    9. Gupta, Rohit & Asgari, Sahar & Moazamigoodarzi, Hosein & Down, Douglas G. & Puri, Ishwar K., 2021. "Energy, exergy and computing efficiency based data center workload and cooling management," Applied Energy, Elsevier, vol. 299(C).
    10. Zhang, Hainan & Tian, Yaling & Tian, Changqing & Zhai, Zhiqiang, 2023. "Effect of key structure and working condition parameters on a compact flat-evaporator loop heat pipe for chip cooling of data centers," Energy, Elsevier, vol. 284(C).
    11. Tian, Tong & Yang, Xuan & Li, Ji, 2025. "To boost waste heat harvesting and power generation through a portable heat pipe battery during high efficient electronics cooling," Applied Energy, Elsevier, vol. 377(PA).
    12. Li Ge & Huaqi Li & Xiaoyan Tian & Zeyu Ouyang & Xiaoya Kang & Da Li & Jianqiang Shan & Xinbiao Jiang, 2022. "Improvement and Validation of the System Analysis Model and Code for Heat-Pipe-Cooled Microreactor," Energies, MDPI, vol. 15(7), pages 1-22, April.
    13. Wang, Haitao & Chen, Yanyan & Luo, Jing & Zhang, Limin & Kang, Huifang & Luo, Ercang & Zhu, Shunmin, 2025. "A novel high-power free-piston stirling engine generator with integrated heat pipes for thermal-to-electric conversion of clean energy," Energy, Elsevier, vol. 314(C).
    14. Yongle Tang & Xuewei Zhang & Zhichun Liu, 2023. "Experimental Study on the Thermal Performance of Flat Loop Heat Pipe Applied in Data Center Cooling," Energies, MDPI, vol. 16(12), pages 1-21, June.
    15. Luo, Zhenbing & He, Wei & Deng, Xiong & Zheng, Mu & Gao, Tianxiang & Li, Shiqing, 2023. "A compacted non-pump self-circulation spray cooling system based on dual synthetic jet referring to the principle of two-phase loop thermosyphon," Energy, Elsevier, vol. 263(PB).

    More about this item

    Keywords

    ;
    ;
    ;
    ;
    ;
    ;

    Statistics

    Access and download statistics

    Corrections

    All material on this site has been provided by the respective publishers and authors. You can help correct errors and omissions. When requesting a correction, please mention this item's handle: RePEc:gam:jeners:v:18:y:2025:i:16:p:4247-:d:1721284. See general information about how to correct material in RePEc.

    If you have authored this item and are not yet registered with RePEc, we encourage you to do it here. This allows to link your profile to this item. It also allows you to accept potential citations to this item that we are uncertain about.

    If CitEc recognized a bibliographic reference but did not link an item in RePEc to it, you can help with this form .

    If you know of missing items citing this one, you can help us creating those links by adding the relevant references in the same way as above, for each refering item. If you are a registered author of this item, you may also want to check the "citations" tab in your RePEc Author Service profile, as there may be some citations waiting for confirmation.

    For technical questions regarding this item, or to correct its authors, title, abstract, bibliographic or download information, contact: MDPI Indexing Manager (email available below). General contact details of provider: https://www.mdpi.com .

    Please note that corrections may take a couple of weeks to filter through the various RePEc services.

    IDEAS is a RePEc service. RePEc uses bibliographic data supplied by the respective publishers.