Abstract
To improve the energy economic efficiency of Data Centers (DCs) in steel enterprises, a centralized heating scheme for waste heat recovery based on the Co-ah cycle is proposed. This scheme establishes a thermoelectric connection between the self-owned power plant of the steel enterprise and the DC, creating a waste heat recovery centralized heating system for a 15 MW DC. The energy efficiency indicators, environmental benefits, economic feasibility, and adaptability of the system are evaluated. The results show that the system can effectively recover waste heat from the DC, significantly reducing cooling electricity consumption during the heating season and decreasing original heating steam consumption by about 25%. Compared to DC using free cooling, the annual operating cost is reduced by 9.7%, with a dynamic payback period for equipment of 6–7 years. The system saves 3,671.5 tons of standard coal and reduces CO2 emissions by 1,615 tons annually compared to DC using isolated free cooling and traditional heating systems. The Improved Power Usage Effectiveness (PUE’) of the system is 1.195, and the Energy Reuse Effectiveness (ERE) is 0.769, outperforming the free cooling’s index of 1.341, although Exergy Reuse Effectiveness (ExRE) is slightly higher than that of free cooling. This system offers mutual benefits for self-owned power plant, DC, and heating companies, achieving a win-win operational state through suitable energy trading prices. The research conclusion provides valuable reference for the future investment and operation of DCs in steel enterprises.
Suggested Citation
Kai Wen & Chengjian Zhou & Xiaopo Wang, 2025.
"The analysis of waste heat recovery in steel enterprises’ data centers based on the Co-ah cycle,"
PLOS ONE, Public Library of Science, vol. 20(5), pages 1-22, May.
Handle:
RePEc:plo:pone00:0323455
DOI: 10.1371/journal.pone.0323455
Download full text from publisher
Corrections
All material on this site has been provided by the respective publishers and authors. You can help correct errors and omissions. When requesting a correction, please mention this item's handle: RePEc:plo:pone00:0323455. See general information about how to correct material in RePEc.
If you have authored this item and are not yet registered with RePEc, we encourage you to do it here. This allows to link your profile to this item. It also allows you to accept potential citations to this item that we are uncertain about.
We have no bibliographic references for this item. You can help adding them by using this form .
If you know of missing items citing this one, you can help us creating those links by adding the relevant references in the same way as above, for each refering item. If you are a registered author of this item, you may also want to check the "citations" tab in your RePEc Author Service profile, as there may be some citations waiting for confirmation.
For technical questions regarding this item, or to correct its authors, title, abstract, bibliographic or download information, contact: plosone (email available below). General contact details of provider: https://journals.plos.org/plosone/ .
Please note that corrections may take a couple of weeks to filter through
the various RePEc services.