Optimization operation of data Center's distributed air conditioning system based on supply-demand matching

Author

Listed:
  • Zhang, Qiaoxin
  • Tu, Rang
  • Yang, Xu

Abstract

A supply-demand matching optimization control of data center's distributed air conditioning system was investigated. For the demand side, an estimation model of a server's cooling air parameters was proposed based on server’ thermal resistance. Test results showed that thermal resistances of servers with power being 6–11 kW were 5.5–9 °C/kW. With the server's heat resistance, chip's temperature and power being known, cooling air outlet temperature and air flow rate can be calculated for different air supply temperature. For the supply side, a mathematic model of the distributed air conditioning system, that combines free cooling and mechanical cooling, was established to calculated energy consumption. Using the above two models, the optimal cooling air supply temperature, which leads to the least power consumption of the air conditioning system can be calculated. Performances of the optimized control method were compared with the conventional control method. Results showed that energy consumption could be saved by 94.4 %, 47.6 % and 31.3 % under the natural cooling mode, the hybrid cooling mode, and the active cooling mode, respectively. Annual energy saving ratios after using the optimized control method in the data center located in Harbin and Kunming were 62.2 % and 45.7 %, respectively.

Suggested Citation

  • Zhang, Qiaoxin & Tu, Rang & Yang, Xu, 2024. "Optimization operation of data Center's distributed air conditioning system based on supply-demand matching," Energy, Elsevier, vol. 306(C).
  • Handle: RePEc:eee:energy:v:306:y:2024:i:c:s0360544224023491
    DOI: 10.1016/j.energy.2024.132575
    as

    Download full text from publisher

    File URL: http://www.sciencedirect.com/science/article/pii/S0360544224023491
    Download Restriction: Full text for ScienceDirect subscribers only

    File URL: https://libkey.io/10.1016/j.energy.2024.132575?utm_source=ideas
    LibKey link: if access is restricted and if your library uses this service, LibKey will redirect you to where you can use your library subscription to access this item
    ---><---

    As the access to this document is restricted, you may want to

    for a different version of it.

    References listed on IDEAS

    as
    1. Eom, Yong Hwan & Yoo, Jin Woo & Hong, Sung Bin & Kim, Min Soo, 2019. "Refrigerant charge fault detection method of air source heat pump system using convolutional neural network for energy saving," Energy, Elsevier, vol. 187(C).
    2. Tong, Zhen & Wang, Wencheng & Fang, Chunxue, 2023. "Energy-saving potential analysis of a CO2 two-phase thermosyphon loop system used in data centers," Energy, Elsevier, vol. 275(C).
    3. Lee, Yee-Ting & Wen, Chih-Yung & Shih, Yang-Cheng & Li, Zhengtong & Yang, An-Shik, 2022. "Numerical and experimental investigations on thermal management for data center with cold aisle containment configuration," Applied Energy, Elsevier, vol. 307(C).
    4. Meng, Xiongzhuang & Zhou, Junli & Zhang, Xuejiao & Luo, Zhiwen & Gong, Hui & Gan, Ting, 2020. "Optimization of the thermal environment of a small-scale data center in China," Energy, Elsevier, vol. 196(C).
    5. Hu, Zhi-Hua & Zheng, Yu-Xin & Wang, You-Gan, 2022. "Packing computing servers into the vessel of an underwater data center considering cooling efficiency," Applied Energy, Elsevier, vol. 314(C).
    6. Sun, Xiaoqing & Zhang, Ce & Han, Zongwei & Dong, Jiaxiang & Zhang, Yiqi & Li, Mengyi & Li, Xiuming & Wang, Qinghai & Wen, Zhenwu & Zheng, Baoli, 2023. "Experimental study on a novel pump-driven heat pipe/vapor compression system for rack-level cooling of data centers," Energy, Elsevier, vol. 274(C).
    Full references (including those not matched with items on IDEAS)

    Citations

    Citations are extracted by the CitEc Project, subscribe to its RSS feed for this item.
    as


    Cited by:

    1. Jiang, Yanhong & Xie, Yibin & Hu, Jingwen & Ma, Binjian & Yang, Huizhu, 2026. "An integrated system for simultaneous heating and dehumidification in dynamic tobacco drying using data center waste heat," Energy, Elsevier, vol. 344(C).
    2. Hong, Xiaoxi & Yao, Ye & Wang, Kui, 2026. "Energy-efficient optimal control of the high-dimensional Air–Water coupled HVAC systems," Energy, Elsevier, vol. 344(C).
    3. Ha, Byeongmin & Lee, Hyeonjeong & Hwangbo, Soonho, 2025. "Towards sustainable energy efficiency: Data-driven optimization in large-scale plants using machine learning applications," Energy, Elsevier, vol. 331(C).

    Most related items

    These are the items that most often cite the same works as this one and are cited by the same works as this one.
    1. Zhang, Ce & Hou, Beiran & Li, Minxia & Dang, Chaobin & Chen, Xun & Li, Xiuming & Han, Zongwei, 2025. "Feasibility analysis of multi-mode data center liquid cooling system integrated with Carnot battery energy storage module," Energy, Elsevier, vol. 320(C).
    2. Xiaofei Huang & Junwei Yan & Xuan Zhou & Yixin Wu & Shichen Hu, 2023. "Cooling Technologies for Internet Data Center in China: Principle, Energy Efficiency, and Applications," Energies, MDPI, vol. 16(20), pages 1-31, October.
    3. Chen, Dong & Chui, Chee-Kong & Lee, Poh Seng, 2025. "Adaptive physically consistent neural networks for data center thermal dynamics modeling," Applied Energy, Elsevier, vol. 377(PD).
    4. Francesco Pelella & Adelso Flaviano Passarelli & Belén Llopis-Mengual & Luca Viscito & Emilio Navarro-Peris & Alfonso William Mauro, 2025. "State-of-the-Art Methodologies for Self-Fault Detection, Diagnosis and Evaluation (FDDE) in Residential Heat Pumps," Energies, MDPI, vol. 18(13), pages 1-22, June.
    5. Zhong, Fangliang & Calautit, John Kaiser & Wu, Yupeng, 2022. "Assessment of HVAC system operational fault impacts and multiple faults interactions under climate change," Energy, Elsevier, vol. 258(C).
    6. Liu, Qingqing & Wang, Ningbo & Guo, Yujie & Shao, Shuangquan, 2025. "Experimental investigation of a dual-evaporator pump-driven loop heat pipe composite system for data centers cooling," Energy, Elsevier, vol. 341(C).
    7. Cheng Liu & Hang Yu, 2021. "Evaluation and Optimization of a Two-Phase Liquid-Immersion Cooling System for Data Centers," Energies, MDPI, vol. 14(5), pages 1-21, March.
    8. Wang, Ningbo & Tian, Bo & Wei, Zuyuan & Guo, Yanhua & Dong, Zijun & Ding, Dekun & Shao, Shuangquan, 2025. "Experimental study of a dual-loop cooling system for data centers: A combined active and passive cooling approach," Energy, Elsevier, vol. 333(C).
    9. Ifaei, Pouya & Tayerani Charmchi, Amir Saman & Loy-Benitez, Jorge & Yang, Rebecca Jing & Yoo, ChangKyoo, 2022. "A data-driven analytical roadmap to a sustainable 2030 in South Korea based on optimal renewable microgrids," Renewable and Sustainable Energy Reviews, Elsevier, vol. 167(C).
    10. Bode, Gerrit & Thul, Simon & Baranski, Marc & Müller, Dirk, 2020. "Real-world application of machine-learning-based fault detection trained with experimental data," Energy, Elsevier, vol. 198(C).
    11. Lee, Jehyung & Jeong, Gil & Choi, Hyungwon & Kim, Hyunjong & Cho, Eunjun & Seo, Beomsoo & Chin, Simon & Kang, Yong Tae, 2025. "Oil circulation rate prediction by transformer based deep learning model in R290 heat pump systems," Energy, Elsevier, vol. 337(C).
    12. Kong, Rui & Zhang, Hainan & Tang, Mingsheng & Zou, Huiming & Tian, Changqing & Ding, Tao, 2024. "Enhancing data center cooling efficiency and ability: A comprehensive review of direct liquid cooling technologies," Energy, Elsevier, vol. 308(C).
    13. Jiang, Feng & Duan, Cuncun & Chen, Bin, 2025. "Facility-level energy-driven water footprint and scarcity implications of Chinese data centers: a bottom-up analysis and scenario-based projection," Applied Energy, Elsevier, vol. 399(C).
    14. Zhang, Yiqi & Li, Mengyi & Dong, Jiaxiang & Zhang, Ce & Li, Xiuming & Han, Zongwei, 2023. "Study on the impacts of refrigerant leakage on the performance and reliability of datacenter composite air conditioning system," Energy, Elsevier, vol. 284(C).
    15. Ren, Shoujun & Yang, Haolin & Wang, Xiaohan, 2021. "The oxygen-deficient combustion and its effect on the NOx emission in a localized stratified vortex-tube combustor," Energy, Elsevier, vol. 235(C).
    16. Wang, Zhi & Peng, Xianyong & Zhou, Huaichun & Cao, Shengxian & Huang, Wenbo & Yan, Weijie & Li, Kuangyu & Fan, Siyuan, 2024. "A dynamic modeling method using channel-selection convolutional neural network: A case study of NOx emission," Energy, Elsevier, vol. 290(C).
    17. Sun, Xiaoqing & Zhang, Ce & Han, Zongwei & Dong, Jiaxiang & Zhang, Yiqi & Li, Mengyi & Li, Xiuming & Wang, Qinghai & Wen, Zhenwu & Zheng, Baoli, 2023. "Experimental study on a novel pump-driven heat pipe/vapor compression system for rack-level cooling of data centers," Energy, Elsevier, vol. 274(C).
    18. Chen, Jianli & Zhang, Liang & Li, Yanfei & Shi, Yifu & Gao, Xinghua & Hu, Yuqing, 2022. "A review of computing-based automated fault detection and diagnosis of heating, ventilation and air conditioning systems," Renewable and Sustainable Energy Reviews, Elsevier, vol. 161(C).
    19. Weijian Ding & Behzad Ebrahimi & Byoung-Do Kim & Connie L. Devenport & Amy E. Childress, 2024. "Analysis of Anthropogenic Waste Heat Emission from an Academic Data Center," Energies, MDPI, vol. 17(8), pages 1-20, April.
    20. Wang, Ningbo & Guo, Yanhua & Huang, Congqi & Tian, Bo & Shao, Shuangquan, 2025. "Multi-scale collaborative modeling and deep learning-based thermal prediction for air-cooled data centers: An innovative insight for thermal management," Applied Energy, Elsevier, vol. 377(PB).

    More about this item

    Keywords

    ;
    ;
    ;
    ;
    ;

    Statistics

    Access and download statistics

    Corrections

    All material on this site has been provided by the respective publishers and authors. You can help correct errors and omissions. When requesting a correction, please mention this item's handle: RePEc:eee:energy:v:306:y:2024:i:c:s0360544224023491. See general information about how to correct material in RePEc.

    If you have authored this item and are not yet registered with RePEc, we encourage you to do it here. This allows to link your profile to this item. It also allows you to accept potential citations to this item that we are uncertain about.

    If CitEc recognized a bibliographic reference but did not link an item in RePEc to it, you can help with this form .

    If you know of missing items citing this one, you can help us creating those links by adding the relevant references in the same way as above, for each refering item. If you are a registered author of this item, you may also want to check the "citations" tab in your RePEc Author Service profile, as there may be some citations waiting for confirmation.

    For technical questions regarding this item, or to correct its authors, title, abstract, bibliographic or download information, contact: Catherine Liu (email available below). General contact details of provider: http://www.journals.elsevier.com/energy .

    Please note that corrections may take a couple of weeks to filter through the various RePEc services.

    IDEAS is a RePEc service. RePEc uses bibliographic data supplied by the respective publishers.