Solution for Effect of Zero Sequence Currents on Y-Y Transformer Differential Protection

Author

Listed:
  • Goutham Pramath H
  • Shaik Nadeem
  • Sunitha N S
  • Narendra kumar k

Abstract

In this paper, Transformer Differential protection mal-operations during external faults due to zero sequence current circulation on one side of the transformer is described with an example 132/33kV 60MVA Y-Y transformer. A simplest and modern solution is recommended with the comparison of conventional technology. Differential protection is a unit protection, which should not issue trip for external faults. When a single phase fault occurred in a transmission line, a small part of zero sequence current feeding from remote end will take a path from one side of the transformer connected to this line. Generally this current is higher than minimum pick-up of Transformer Differential protection. Since there will be no reflected current on other side of the transformer corresponding to this fault current, transformer differential protection can issue trip when this zero sequence current is higher than pick-up value. This scenario is simulated in MiPower software by considering HV side of the transformer connected to the grid via a transmission line and LV side is connected to strong, weak and no source cases to observe zero sequence current flow in transformer. These results are verified with manual calculations also. Generally zero sequence currents during external faults will cause mal operations of transformer differential protection for Yd and Dy type transformers. But this paper explains a different scenario with Y-Y transformers differential protection mal operation for eternal transmission line faults. Recently this problem is facing by many of the solar plant substations even with YN-yn transformers and generating plants. Hence a solution is prepared with numerical relay of ABB make RET670 and prepared solution is tested in the laboratory for the disturbance took place in a 132kV substation using Omicron injection unit. Conventional solution during electromechanical and static relays with interposing delta connected CT to filter zero sequence currents for external faults is also described in this paper.

Suggested Citation

  • Goutham Pramath H & Shaik Nadeem & Sunitha N S & Narendra kumar k, 2018. "Solution for Effect of Zero Sequence Currents on Y-Y Transformer Differential Protection," International Journal of Scientific Research in Computer Science, Engineering and Information Technology, International Journal of Scientific Research in Computer Science, Engineering and Information Technology, vol. 4(6), pages 793-802, May.
  • Handle: RePEc:jbh:ijsrcs:v4:y2018:i6:id:hcseit1846150
    Note: Article URL: https://ijsrcseit.com/CSEIT1846150
    as

    Download full text from publisher

    File URL: https://ijsrcseit.com/CSEIT1846150
    File Function: Article URL
    Download Restriction: no

    File URL: https://ijsrcseit.com/paper/CSEIT1846150.pdf
    File Function: Full text
    Download Restriction: no
    ---><---

    More about this item

    Keywords

    ;
    ;
    ;
    ;
    ;

    Statistics

    Access and download statistics

    Corrections

    All material on this site has been provided by the respective publishers and authors. You can help correct errors and omissions. When requesting a correction, please mention this item's handle: RePEc:jbh:ijsrcs:v4:y2018:i6:id:hcseit1846150. See general information about how to correct material in RePEc.

    If you have authored this item and are not yet registered with RePEc, we encourage you to do it here. This allows to link your profile to this item. It also allows you to accept potential citations to this item that we are uncertain about.

    We have no bibliographic references for this item. You can help adding them by using this form .

    If you know of missing items citing this one, you can help us creating those links by adding the relevant references in the same way as above, for each refering item. If you are a registered author of this item, you may also want to check the "citations" tab in your RePEc Author Service profile, as there may be some citations waiting for confirmation.

    For technical questions regarding this item, or to correct its authors, title, abstract, bibliographic or download information, contact: Pankaj Sharma (USA) (email available below). General contact details of provider: https://ijsrcseit.com/home .

    Please note that corrections may take a couple of weeks to filter through the various RePEc services.

    IDEAS is a RePEc service. RePEc uses bibliographic data supplied by the respective publishers.