Abstract

The paper presents the Fractional Fourier Transform-Singular Value Decomposition (FRFT-SVD) method for the localization of various power system faults in a 200 km long, 500 kV Egyptian transmission line using sent end-line current signals. Transient simulations are carried out using Alternating Transient Program/Electromagnetic Transient Program (ATP-EMTP), and the outcomes are then examined in MATLAB to carry out a sensitivity analysis against measurement noises, sampling frequency, and fault characteristics. The proposed work employs current fault signals of five distinct kinds at nineteen intermediate points throughout the length of the line. The approach utilized to construct the localizer model is FRFT-SVD. It is much more effortless, precise, and effective. The FRFT-SVD is utilized in this technique to calculate 19 sets of indices of the greatest S value throughout the length of the line. The FRFT-SVD localizer model is also designed to be realistic, with power system noise corrupting fault signals. To generate fault curves, the curve fitting technique is applied to these 19 sets of indices. Reduced chi-squared and modified R-squared criteria are used to choose the best-suited curve. The proposed work results in a very precise localization, with only a 0.0016% average percentage error for fault localization and a maximum percentage error of 0.002% for the 200 km Egyptian transmission line. Finally, this work can be employed as a proper link between the nuclear power plant and the grid. The proposed method is an efficient fault distance estimation method that might contribute to creating a dependable transient-based approach to power system protection.

Suggested Citation

  • Mohamed H. Saad & Mostafa M. Fouda & Abdelrahman Said, 2023. "A New Method of Fault Localization for 500 kV Transmission Lines Based on FRFT-SVD and Curve Fitting," Energies, MDPI, vol. 16(2), pages 1-23, January.
  • Handle: RePEc:gam:jeners:v:16:y:2023:i:2:p:758-:d:1029744
    as

    Download full text from publisher

    File URL: https://www.mdpi.com/1996-1073/16/2/758/pdf
    Download Restriction: no

    File URL: https://www.mdpi.com/1996-1073/16/2/758/
    Download Restriction: no
    ---><---

    Corrections

    All material on this site has been provided by the respective publishers and authors. You can help correct errors and omissions. When requesting a correction, please mention this item's handle: RePEc:gam:jeners:v:16:y:2023:i:2:p:758-:d:1029744. See general information about how to correct material in RePEc.

    If you have authored this item and are not yet registered with RePEc, we encourage you to do it here. This allows to link your profile to this item. It also allows you to accept potential citations to this item that we are uncertain about.

    We have no bibliographic references for this item. You can help adding them by using this form .

    If you know of missing items citing this one, you can help us creating those links by adding the relevant references in the same way as above, for each refering item. If you are a registered author of this item, you may also want to check the "citations" tab in your RePEc Author Service profile, as there may be some citations waiting for confirmation.

    For technical questions regarding this item, or to correct its authors, title, abstract, bibliographic or download information, contact: MDPI Indexing Manager (email available below). General contact details of provider: https://www.mdpi.com .

    Please note that corrections may take a couple of weeks to filter through the various RePEc services.

    IDEAS is a RePEc service. RePEc uses bibliographic data supplied by the respective publishers.