IDEAS home Printed from https://ideas.repec.org/a/gam/jeners/v15y2022i12p4323-d837784.html
   My bibliography  Save this article

Experimental and Numerical Investigation of Extinguishing Effectiveness of Inert-Gas Agents in a Leaky Enclosure

Author

Listed:
  • Xiaoqin Hu

    (Department of Safety, Chemical and Biomedical Laboratory Sciences, Faculty of Engineering and Sciences, Western Norway University of Applied Sciences, 5528 Haugesund, Norway)

  • Arjen Kraaijeveld

    (Department of Safety, Chemical and Biomedical Laboratory Sciences, Faculty of Engineering and Sciences, Western Norway University of Applied Sciences, 5528 Haugesund, Norway)

Abstract

Gas-fire-suppression systems are currently applied to some specific buildings in Norway, as sprinkler systems may not provide sufficient protection in some cases. The application of inert-gas-fire-suppression systems for hazard class 6 buildings needs further intensive validation by experimental and numerical study. Due to the presence of cracks and ventilation systems, it becomes doubtful whether inert-gas agents can extinguish a deep-seated fire located in a leaky enclosure. In this study, tests and numerical simulations were both conducted to investigate the extinguishing effectiveness of inert-gas agents for a closet fire in a leaky apartment. The results show that the location of cracks plays a nonnegligible role in determining the oxygen level in the leaky apartment. The tests and simulations demonstrated that the gas-fire-suppression system successfully extinguished the closet fire even if the activation of the gas-fire-suppression system was postponed or the path available for the inert-gas agent to reach the fire source was narrowed. However, the sprinkler system failed to achieve this. The experimental data also demonstrated that the calculation method proposed in our previous work can be used to estimate the oxygen level in a leaky enclosure.

Suggested Citation

  • Xiaoqin Hu & Arjen Kraaijeveld, 2022. "Experimental and Numerical Investigation of Extinguishing Effectiveness of Inert-Gas Agents in a Leaky Enclosure," Energies, MDPI, vol. 15(12), pages 1-14, June.
  • Handle: RePEc:gam:jeners:v:15:y:2022:i:12:p:4323-:d:837784
    as

    Download full text from publisher

    File URL: https://www.mdpi.com/1996-1073/15/12/4323/pdf
    Download Restriction: no

    File URL: https://www.mdpi.com/1996-1073/15/12/4323/
    Download Restriction: no
    ---><---

    Corrections

    All material on this site has been provided by the respective publishers and authors. You can help correct errors and omissions. When requesting a correction, please mention this item's handle: RePEc:gam:jeners:v:15:y:2022:i:12:p:4323-:d:837784. See general information about how to correct material in RePEc.

    If you have authored this item and are not yet registered with RePEc, we encourage you to do it here. This allows to link your profile to this item. It also allows you to accept potential citations to this item that we are uncertain about.

    We have no bibliographic references for this item. You can help adding them by using this form .

    If you know of missing items citing this one, you can help us creating those links by adding the relevant references in the same way as above, for each refering item. If you are a registered author of this item, you may also want to check the "citations" tab in your RePEc Author Service profile, as there may be some citations waiting for confirmation.

    For technical questions regarding this item, or to correct its authors, title, abstract, bibliographic or download information, contact: MDPI Indexing Manager (email available below). General contact details of provider: https://www.mdpi.com .

    Please note that corrections may take a couple of weeks to filter through the various RePEc services.

    IDEAS is a RePEc service. RePEc uses bibliographic data supplied by the respective publishers.