Abstract
According to NEC 240.101 regulations each and every component of a power system distribution network has to have an over-current protective device (OCPD) for its protection. The OCPDs must coordinate with other devices both upstream and downstream for a reliable operation and protection of the power systems distribution network. There are four equipment/components for the IEEE 13 node radial test feeder each modelled in this paper to be protected by fuses. These components are namely the nodes, the underground cables, the overhead distribution lines and the transformers. Equipment protection is an important and necessary exercise of performing power systems protection coordination processes. The equipment and their over-current protective device’s time-current characteristic (TCC) curves are important tools used to show and to indicate the protection requirements, landmark points and damage curves for all power systems equipment. Individual equipment protection requirements and limitations are described and identified by use of their various landmarks and damage curves. These damage curves and the landmark points are all superimposed with the Time-Current Characteristic curves of the Over-Current Protective Devices used in protecting the equipment on one composite TCC graph. Equipment damage curves which fall to the right and above the Over-Current Protective Device’s TCC curves with sufficient margins are considered to be protected by the OCPDs. Equipment damage curves which fall to the left and below the OCPD’s TCC curves are considered not to be protected by the OCPDs. IEEE Standard 241 states that on all power systems, the OCPDs should be selected and set to open before the Ampacity mark, the short circuit damage curves, and both the thermal and the mechanical damage curves limits of the protected components are exceeded. This paper presents a detailed Fuse-Fuse protection scheme for the IEEE 13 node radial test feeder as modeled on the Electrical Transients Analysis Program (ETAP).
Suggested Citation
Kemei Peter Kirui & David K. Murage & Peter K. Kihato, 2019.
"Fuse-Fuse Protection Scheme ETAP Model for IEEE 13 Node Radial Test Distribution Feeder,"
European Journal of Engineering and Technology Research, European Open Science, vol. 4(9), pages 224-234, September.
Handle:
RePEc:epw:ejeng0:v:4:y:2019:i:9:id:61549
DOI: 10.24018/ejeng.2019.4.9.1549
Download full text from publisher
Corrections
All material on this site has been provided by the respective publishers and authors. You can help correct errors and omissions. When requesting a correction, please mention this item's handle: RePEc:epw:ejeng0:v:4:y:2019:i:9:id:61549. See general information about how to correct material in RePEc.
If you have authored this item and are not yet registered with RePEc, we encourage you to do it here. This allows to link your profile to this item. It also allows you to accept potential citations to this item that we are uncertain about.
We have no bibliographic references for this item. You can help adding them by using this form .
If you know of missing items citing this one, you can help us creating those links by adding the relevant references in the same way as above, for each refering item. If you are a registered author of this item, you may also want to check the "citations" tab in your RePEc Author Service profile, as there may be some citations waiting for confirmation.
For technical questions regarding this item, or to correct its authors, title, abstract, bibliographic or download information, contact: Support (email available below). General contact details of provider: https://eu-opensci.org/index.php/ejeng .
Please note that corrections may take a couple of weeks to filter through
the various RePEc services.