IDEAS home Printed from https://ideas.repec.org/a/gam/jeners/v12y2019i22p4307-d286098.html
   My bibliography  Save this article

Development of Virtual Air Flow Sensor Using In-Situ Damper Performance Curve in VAV Terminal Unit

Author

Listed:
  • Hyo-Jun Kim

    (Department of Architectural Engineering, Graduate School of Yeungnam University, 280 Daehak-Ro, Gyeongsan 38541, Korea)

  • Jae-Hun Jo

    (Division of Architecture, Inha University, 100 Inha-ro, Incheon 22212, Korea)

  • Young-Hum Cho

    (School of Architecture, Yeungnam University, 280 Daehak-Ro, Gyeongsan 38541, Korea)

Abstract

In this study, we developed a virtual air flow sensor using an in-situ damper performance curve to secure the stability of control of the variable air volume (VAV) terminal unit, and also established the in-situ measurement procedure. The minimum air flow rate of the VAV terminal unit was related to the energy consumption, it was important to determine the minimum air flow rate suitable for the situation of each room in terms of energy saving. However, it was difficult to set the minimum air flow rate low setpoint due to the low accuracy of the air flow sensor of the VAV terminal unit. This paper suggested a virtual air flow sensing method using an in-situ damper performance curve in the VAV terminal unit. The input factors of the virtual sensor were developed on the basis of the supply fan speed and damper opening ratio, which could be easily obtained from the existing control system. In addition, the in-situ measurement procedure of the virtual air flow sensor was developed by dividing the procedure into five steps. Finally, reliability of the virtual air flow sensor was evaluated through uncertainty analysis of input variables and relative error analysis, in comparison with the conventional air flow rate measurement method. The developed virtual air flow sensor was found to have an uncertainty of up to 8.8%, and it was also found that the closer to the maximum the values of the input variables, the lower the uncertainty. In addition, verification of relative error with respect to the measured values by the hot-wire anemometer was conducted by varying operation conditions to a total of 12 cases, and as a result, relative error was found to be up to 5.6%. In addition, the results of long-term experiment showed that relative error was within about 9.5%, and thus, the feasibility for field application and control was confirmed.

Suggested Citation

  • Hyo-Jun Kim & Jae-Hun Jo & Young-Hum Cho, 2019. "Development of Virtual Air Flow Sensor Using In-Situ Damper Performance Curve in VAV Terminal Unit," Energies, MDPI, vol. 12(22), pages 1-14, November.
  • Handle: RePEc:gam:jeners:v:12:y:2019:i:22:p:4307-:d:286098
    as

    Download full text from publisher

    File URL: https://www.mdpi.com/1996-1073/12/22/4307/pdf
    Download Restriction: no

    File URL: https://www.mdpi.com/1996-1073/12/22/4307/
    Download Restriction: no
    ---><---

    References listed on IDEAS

    as
    1. Ji-Hyun Shin & Yong-In Kim & Young-Hum Cho, 2019. "Development of Operating Method of Multi-Geothermal Heat Pump Systems Using Variable Water Flow Rate Control and a COP Prediction Model Based on ANN," Energies, MDPI, vol. 12(20), pages 1-18, October.
    2. Hyo-Jun Kim & Young-Hum Cho, 2017. "A Study on a Control Method with a Ventilation Requirement of a VAV System in Multi-Zone," Sustainability, MDPI, vol. 9(11), pages 1-17, November.
    Full references (including those not matched with items on IDEAS)

    Citations

    Citations are extracted by the CitEc Project, subscribe to its RSS feed for this item.
    as


    Cited by:

    1. Hyo-Jun Kim & Ji-Hyun Shin & Jae Hun Jo & Young-Hum Cho, 2020. "Development of Air Flow Rate Prediction Model Using Multiple Regression in VAV Terminal Unit," Energies, MDPI, vol. 13(10), pages 1-10, May.

    Most related items

    These are the items that most often cite the same works as this one and are cited by the same works as this one.
    1. Hyo-Jun Kim & Young-Hum Cho, 2021. "Optimal Control Method of Variable Air Volume Terminal Unit System," Energies, MDPI, vol. 14(22), pages 1-15, November.
    2. Behzad Rismanchi & Juan Mahecha Zambrano & Bryan Saxby & Ross Tuck & Mark Stenning, 2019. "Control Strategies in Multi-Zone Air Conditioning Systems," Energies, MDPI, vol. 12(3), pages 1-14, January.
    3. Ji-Hyun Shin & Hyo-Jun Kim & Han-Gyeol Lee & Young-Hum Cho, 2023. "Variable Water Flow Control of Hybrid Geothermal Heat Pump System," Energies, MDPI, vol. 16(17), pages 1-18, August.
    4. Dimitris Katsaprakakis & Vasilis Kagiamis & George Zidianakis & Luca Ambrosini, 2019. "Operation Algorithms and Computational Simulation of Physical Cooling and Heat Recovery for Indoor Space Conditioning. A Case Study for a Hydro Power Plant in Lugano, Switzerland," Sustainability, MDPI, vol. 11(17), pages 1-36, August.
    5. Jeong Soo Shin & Jong Woo Park & Sean Hay Kim, 2020. "Measurement and Verification of Integrated Ground Source Heat Pumps on a Shared Ground Loop," Energies, MDPI, vol. 13(7), pages 1-24, April.
    6. Sebastian Angermeier & Christian Karcher, 2020. "Model-Based Condenser Fan Speed Optimization of Vapor Compression Systems," Energies, MDPI, vol. 13(22), pages 1-26, November.

    Corrections

    All material on this site has been provided by the respective publishers and authors. You can help correct errors and omissions. When requesting a correction, please mention this item's handle: RePEc:gam:jeners:v:12:y:2019:i:22:p:4307-:d:286098. See general information about how to correct material in RePEc.

    If you have authored this item and are not yet registered with RePEc, we encourage you to do it here. This allows to link your profile to this item. It also allows you to accept potential citations to this item that we are uncertain about.

    If CitEc recognized a bibliographic reference but did not link an item in RePEc to it, you can help with this form .

    If you know of missing items citing this one, you can help us creating those links by adding the relevant references in the same way as above, for each refering item. If you are a registered author of this item, you may also want to check the "citations" tab in your RePEc Author Service profile, as there may be some citations waiting for confirmation.

    For technical questions regarding this item, or to correct its authors, title, abstract, bibliographic or download information, contact: MDPI Indexing Manager (email available below). General contact details of provider: https://www.mdpi.com .

    Please note that corrections may take a couple of weeks to filter through the various RePEc services.

    IDEAS is a RePEc service. RePEc uses bibliographic data supplied by the respective publishers.