Abstract

At PT Borneo Alumina Indonesia (PT BAI), the D01 Power Distribution System uses circuit breakers (CB) with a current rating capacity of 1250A for both incoming and outgoing 10kV busbars. Replacing outgoing CBs with the same capacity during maintenance leads to unnecessary waste. This study was conducted to examine the appropriate CB capacity as a substitute for the old CBs in the outgoing 10 kV busbars for loads of 10 kV induction motors and transformers so that recommendations can be made to improve efficiency during maintenance on the D01 Power Distribution System. The Electronic Transient Analyzer Program (ETAP) 19.0.1 software was used to perform short circuit simulations based on IEC 60909 and load flow simulations, which were then adjusted to IEC 60059 and CB products from Siemens. The results show that we can replace the current Siemens CB, which has a rated breaking current specification of 31.5kA, with 25kA during the maintenance period. We can also replace the rated peak value of 80kA with 63kA, and the rated current of 1250A with 630A. Replacement of CB specifications does not change/modify the switchgear panel because the replacement CB matches the brand, dimensions, and size of the currently installed CB. These findings would also help increase efficiency during maintenance on the D01 Power Distribution System. The discussion includes limitations and recommendations for future research.

Suggested Citation

  • Agustino Al Hakim & Rudy Gianto & Purwoharjono & Rudi Kurnianto & Ismail Yusuf, 2024. "An analysis of circuit breaker capacity according to IEC 60909 and IEC 60059 standards at the PT Borneo Alumina Indonesia electrical system," Edelweiss Applied Science and Technology, Learning Gate, vol. 8(4), pages 290-308.
  • Handle: RePEc:ajp:edwast:v:8:y:2024:i:4:p:290-308:id:969
    as

    Download full text from publisher

    File URL: https://learning-gate.com/index.php/2576-8484/article/view/969/255
    Download Restriction: no
    ---><---

    Corrections

    All material on this site has been provided by the respective publishers and authors. You can help correct errors and omissions. When requesting a correction, please mention this item's handle: RePEc:ajp:edwast:v:8:y:2024:i:4:p:290-308:id:969. See general information about how to correct material in RePEc.

    If you have authored this item and are not yet registered with RePEc, we encourage you to do it here. This allows to link your profile to this item. It also allows you to accept potential citations to this item that we are uncertain about.

    We have no bibliographic references for this item. You can help adding them by using this form .

    If you know of missing items citing this one, you can help us creating those links by adding the relevant references in the same way as above, for each refering item. If you are a registered author of this item, you may also want to check the "citations" tab in your RePEc Author Service profile, as there may be some citations waiting for confirmation.

    For technical questions regarding this item, or to correct its authors, title, abstract, bibliographic or download information, contact: Melissa Fernandes (email available below). General contact details of provider: https://learning-gate.com/index.php/2576-8484/ .

    Please note that corrections may take a couple of weeks to filter through the various RePEc services.

    IDEAS is a RePEc service. RePEc uses bibliographic data supplied by the respective publishers.